Product Brief
GIS
TBEA is one of the few enterprises in the industry with the research and development capacity of 1000kV UHV switch. The GIS developed by TBEA, such as 126kV, 145kV, 252kV and 550kv GIS, 145kV porcelain column circuit breaker, 550kV and 800kV tank circuit breaker, 40.5kV, 126kV and 252kV disconnectors, fully meet the IEC / GB / DL standards, and their performance has reached the international advanced and domestic leading level of similar products.
- Specification & Series:72.5kV~145kV GIS——720bays
170kV~252kV GIS——480bays
420kV~550kV GIS——48bays
SERVICE CALL+86 13521339794
Price Inquiry
Online Remarks
enfi.cemsa@gmail.com
Advantages & Features
- 132/220/550kv GIS is modular design. The live part of the product is completely sealed in the metal shell and insulated by SF6 gas, which prevents the invasion of foreign matters outside, and ensures the good insulation performance of the product.
- Due to modular design, the design and installation are flexible, which greatly meet the requirements of customers;
- The product is small in volume and light in weight;
- Compact structure, space saving;
- The whole transportation is convenient for installation;
- The opening ability is strong and the insulation level is high;
- Product safety, reliability, stable operation.
Working Principle
SF6 gas is used as the insulating medium, and the main circuit conductor is enclosed in the gas chamber by the grounded metal shell, including the electrical function modules such as circuit breaker, isolation (grounding) switch, current transformer, voltage transformer, main bus line, incoming and outgoing bushing; Each combination is equipped with a local control cabinet, which configures various monitoring and secondary control components in the cabinet. The action of each element in GIS equipment is controlled by the principle of relay protection, realizing the function of interlocking locking, meeting the requirements of system eliminating fault and switching power load.
Technical Parameters
Serial number | Product model | Company | ZF53-126 | ZF53-145 | IFT-252 | ZF53-550 |
---|---|---|---|---|---|---|
1 | Maximum ambient temperature | Temperature | 40 | 40 | 40 | 40 |
2 | Ambient minimum temperature | Temperature | -30 | -30 | -25 | -30 |
3 | altitude | M | 1000/2000 | 1000 | 1000/1900 | 1000 |
4 | Pollution level | Class III / altitude 2600m Class IV / altitude 1000M |
Class III / altitude 1300m | Class III / altitude 1900m Class IV / altitude 1000M |
IV | |
5 | Rated voltage | KV | 126 | 145 | 252 | 550 |
6 | Rated current | A | 2000 | 3150 | 3150/4000 | 4000/5000 |
7 | Rated frequency | Hz | 50 | 50 | 50 | 50 |
8 | Rated short-time power frequency withstand voltage (effective value between phase to ground, phase to phase / fracture) |
KV | 230/230+73 | 275/315 | 460/460+145 | 740/740+318 |
9 | Rated lightning impulse withstand voltage (peak value between phase to phase / fracture) |
KV | 550/550+103 | 650/750 | 1050/1050+206 | 1675/1675+450 |
10 | Rated operating impulse withstand voltage (phase to ground, phase to phase / peak between fractures) |
Not applicable | Not applicable | Not applicable | 1300/1175+450 | |
11 | Rated short-time withstand current (effective value) |
KA | 40 | 40 | 50 | 63 |
12 | Rated short circuit duration | S | 4 | 4 | 3 | 3 |
13 | Rated withstand current (peak) | KA | 100 | 100 | 125 | 171 |
14 | Annual leakage rate of SF6 gas (no more than) |
%/Y | 0.005 | 0.005 | 0.005 | 0.005 |
15 | Air chamber of circuit breaker | MPa | 0.58 | 0.58 | 0.6 | 0.58 |
15 | Other gas chambers | MPa | 0.45 | 0.58 | 0.6 | 0.48 |
16 | Rated operating sequence | O–0.3s–CO–180s–CO | O–0.3s–CO–180s–CO | O–0.3s–CO–180s–CO | O–0.3s–CO–180s–CO | |
17 | Operation mode of circuit breaker | Spring | Spring | Spring or hydraulic | hydraulic pressure | |
18 | Operation mode of disconnector / grounding switch | Electric operation, manual | Electric operation, manual | Electric operation, manual | Electric operation, manual | |
19 | Operation mode of fast grounding switch | Electric spring operation, manual | Electric spring operation, manual | Electric spring operation, manual | Electric spring operation, manual | |